CPM 0600 Control Point Module

Features Tech Specs Datasheets
Proven, Secure, Multi-Application
Secure: built on industry leading security features.
Reliable: provides a 20 year life.
Extensible: connects to local devices to the NES System.
CPM 0600 System
Open Standard, Reliable Platform
The CPM 0600 Control Point Module is a printed circuit board assembly modules that include everything required for reliable OSGP communication including power line communications chip, microprocessor, memory, full OSGP stack and power line coupling circuit. With this module, partners can quickly integrate their existing products including legacy or smart meters, or build new devices seamlessly with the NES system.
CPM 0600 Control Point Module Features CPM 0600 Features
  • Interoperable sub-system within NES’s proven three-tier smart metering and grid system
  • Complete OSGP implementation
  • Supports remote firmware, upgrades and reconfiguration
  • Enables time-of-use metering
  • 4x16 channel data logging and load profiling
  • Comprehensive event, outage, and informational logging
  • Enables maximum power or average power based load limiting
  • Optional time-based and on demand direct load control
  • Equipped with power line communications transceiver and coupling circuit 
Transform Your Product into a Smart Grid Sensing and Control Point
CPM 0600 Grid Sensing
  • A wide array of I/O signals let you adapt the module to a variety of devices
  • Web services let users read and write high and low priority alarms and events
  • Automated NES discovery and topology mapping shows which utility transformer is serving connected devices
  • Interoperable sub-system within NES' proven three-tier smart metering and grid system
Reduce Development Time, Expense and Risk
CPM 0600 Grid Control
  • Reduces development time and expense, providing secure and scalable device control.
  • Development program provides hardware, software, training, and support - including power line coupling circuit design review by experienced NES support staff. 
  • Complete OSGP implementation.
Offer a Market-Leading Smart Grid System that Leverages Your Local Market Expertise
CPM 0600 Smart Grid System
  • Comprehensive event, outage, and informational logging
  • Enables 4x16 channel data logging and load profiling and time-of-use metering 
  • Supports remote firmware upgrades and reconfiguration
Expand Your Opportunity with a Proven, Market-Leading Smart Grid System
CPM 0600 Leading Grid Software
  • Managed by DCN 3000 Distributed Control Node or DCN 1000 Data Concentrators, Control Point modules allow intelligent control for nearly real-time response to local smart grid conditions
Technical Specs
Network Communication CENELEC A-band-compliant power line communication with built-in coupling circuit complies with the ETSI TS 103 908 Power Line Telecommunications (PLT) BPSK Narrow Band Power Line Channel for Smart Metering Applications specification. Application layer compatible with the ETSI GS OSG 001 Open Smart Grid Protocol.
 
 
Power input 12V +/- 10% DC @ 70 mA typical, 350 mA while communicating. An additional 16mA is added when using the optional load control relay (and relay is active). External 3V lithium battery is required (2.5V minimum, 3.6V maximum)
 
 
Integration connector 20 pins (10x2), 2mm pitch, meant for soldering. 4 pins (2x2) for mains voltage (Live – Neutral)
  • I/O interface (TTL-level only)
  • 1 secure Multipurpose Expansion Port (MEP) serial interface to connect to the attached smart meter
  • 1 set of disconnect control signals. Disconnect control is also available programmatically through the MEP interface
  • 1 input for disconnect status. Status also available programmatically through the MEP communication interface
  • 1 tamper switch input
  • 1 set of signals for optical port interface
  • 1 input for register protect
  • 1 input for hardware reset
  • 1 output (pull-down resistor) to indicate that the CPM 0600 is connected to a host device
  • 1 optional single-pole voltage-free relay; maximum load rating is 250V, 5A; fully isolated. Enables locally controlled, schedule-based and over the network, on-demand direct load control operations. Schedules can be remotely updated over the network
 
 
 Real Time Clock Real-time clock accurate per IEC 62052-21/62054-21 to +/- 0.5 seconds per day
 
 
Temperature Specified operating range: -40° C to +85° C. Specified storage range: -40° C to +85° C
 
 
Humidity <= 95% RH non-condensing
 
 
Board
Dimensions
82mm x 42mm x 23mm